about 2000m ³ weld inspection of lng storage tank


about 2000m ³ for the weld inspection of lng storage tank, the weld must be visually inspected, and the weld height, width and undercut amount shall meet the requirements in the table below.


list of weld appearance quality requirements



weld detection shall be carried out according to the requirements of design documents and specifications. the specific requirements are as follows:


1. the butt weld of the main body of the inner groove shall be subject to 100% rt nondestructive testing according to jb / t4730.2-2005, and it is qualified at level ii.


2. the butt weld of the main body of the outer groove shall be tested by 100% pt coloring according to jb / t4730.2-2005, and it is qualified at level i.


3. the fillet weld between the inner and outer groove bottom plate and the cylinder shall be subject to 100% pt coloring inspection, and the leakage inspection shall be carried out with a vacuum box.


4. pipeline inspection requirements: for liquid phase pipeline, all butt welds shall be subject to 100% rt radiographic inspection, and class ii is qualified; for gas phase pipeline, when dn > 20, 100% radiographic inspection shall be conducted for butt weld, which is qualified in grade ii; when dn ≤ 20, pt is used for detection, and class i is qualified; pt test was conducted for all fillet welds, and it was qualified as grade i. all tests shall be carried out in accordance with jb / t4730.2-2005.