hotline
86 512-81666096180、pressure measurement and control measures of large liquid ammonia cryogenic liquid full capacity tank - doer equipment
classification:forum publishtime:2021-07-24 13:30:53
pressure measurement and control measures of large liquid ammonia cryogenic liquid full capacity tank
the pressure measurement and control measures of large liquid ammonia low temperature liquid full capacity tank are due to the rise of tank pressure caused by heat transfer and liquid ammonia evaporation. in addition, the gas displaced when the storage tank is filled with liquid ammonia will also cause the pressure of the storage tank to rise. in order to maintain the pressure in the tank within the normal operating range, the liquid ammonia storage tank is equipped with a pressure measurement, control and regulation system. two expiratory relief valves and three vacuum suction valves are installed on the top of each storage tank as a measure to protect the storage tank from damage.
if the tank pressure deviates from the controllable range, the pressure is too high or too low. the storage tank is designed with multi-layer safety protection measures to prevent overpressure of the storage tank: 1) recover the gas evaporated from the storage tank through bog pipeline; 2) discharge the gas from the storage tank into the low-pressure flare through the vent pipeline; 3) the exhalation relief valve jumps to discharge the gas of the storage tank to the low-pressure flare; 4) emergency safety shutdown;
safety protection sequence to prevent low tank pressure: 1) reduce the amount of gas recovered by bog pipeline; 2) fill the tank with liquid ammonia or nitrogen; 3) the tank suction valve replenishes air to the tank.
in order to ensure the reliability of pressure detection, the storage tank is equipped with 4 sets of pressure transmitters to output 4 ~ 20ma signals to the user's dcs and sis system, with hart protocol. the storage tank pressure is displayed and recorded in the control room. local pressure indication is set on the tank top, and the tank pressure is automatically controlled by dcs system.
news
- 205、lng operating procedures - doer equipment [2022-11-15]
- 205. tank classification and characteristics - doer… [2022-11-15]
- 204. brief introduction to tank development - doer … [2022-10-31]
- 204、lng vacuum cryogenic liquid storage tank - doe… [2022-10-31]
- 203、precautions for precooling of natural gas stor… [2022-10-28]
- 203、preparation before pressure regulation of lng … [2022-10-24]
- 3,successful test run of cangzhou ethylene storage… [2019-09-02]
- 2,advantages of suzhou doer large cryogenic tank … [2019-08-30]
- 1,congratulations on the success of one-time liqui… [2019-08-26]